Online transformerless UPS HC900RT 1 kVA -10 kVA (120 V)

 On-line high frequency UPS HC 900RT 1 kVA ~ 10 kVA (120 V) is the high density version of on-line double-conversion UPS for application to voltage 100 V / 110 V / 115 V / 120 V / 127 Vac.


details

Description of this Online transformerless UPS HC900RT 1 kVA -10 kVA (120 V)
 
 On-line high frequency UPS HC 900RT 1 kVA ~ 10 kVA (120 V) is the high density version of on-line double-conversion UPS for application to voltage 100 V / 110 V / 115 V / 120 V / 127 Vac, It is equipped with input power factor correction (PFC), output power factor 0.9 offering high levels of reliability and high operating efficiency for IT systems, small computer room,telecommunications equipment,office terminal ,automation equipment and mission critical systems. The UPS is Rack and tower convertible, and takes up only 2-3U in height.It has fault self-diagnosis and self-protection function. The fault information is clear at a glance, and the maintenance work is quick and easy.Charging design with automatic floating charge switching.
1.Based on DSP's fully digital control technology, the control circuit is simplified, and the flexibility and reliability of the circuit are higher.
2.Power device design has large margin and system operation is more reliable.
3.Built-in EMC filter and dual anti-surge protection, the load is safer.
4.PFC input power factor correction technology to reduce input harmonic current and reduce pollution to the power grid.
5.Meet ROHS requirements and meet the high electromagnetic compatibility standard ClassB.
6.Pure online double conversion design to isolate and filter out various harmonics and faults of the power grid.
7.ECO economic working mode selection function, reducing energy consumption, operating efficiency of up to 94%.
8.Intelligent fan speed control to reduce noise and save energy.
9.High power density design, occupying a small space, and the whole machine runs more efficiently.
10.Rack and tower compatible design, 19-inch rack and tower installation freely.
11.220V, 50Hz/60Hz power standard can be flexibly set by the panel.
12.The LCD display mode is different from the random installation or tower installation mode, and it can be rotated freely for user's convenience.
13.Simply increase the backup time by adding battery modules.
 
Specification of this Online transformerless UPS HC900RT 1 kVA -10 kVA (120 V)
 
 

MODEL

HC901RT

HC902RT

HC903RT

HC906RT

HC9010RT

Capacity

1 kVA / 900 W

2 kVA / 1800 W

3 kVA / 2700 W

6 kVA / 5400 W

10 kVA / 9000 W

INPUT

Rated voltage

100 V / 110 V / 115 V / 120 V / 127 Vac

208 V / 220 V / 230 V / 240 Vac

Voltage range

(55 ~ 145) ± 5 Vac (60% load); (65 ~ 145) ± 5Vac(70% load)
(75 ~ 145) ± 5 Vac (80% load); (85 ~ 145) ± 5Vac(100% load)

Half load (115 ~ 295) ± 5Vac
Full load (165 ~ 295) ± 5Vac

Frequency

45 ~ 55 Hz ± 0.5% or 55 ~ 65 Hz ± 0.5% (auto-sense)

40 ~ 70 Hz ± 0.5% (auto-sense)

Power factor

≥ 0.98

≥ 0.99

Bypass voltage range

(95 ~ 135) ± 5 Vac

160 V ~ 252 Vac or (95 ~ 135) ± 5 Vac

OUTPUT

Voltage

100 V / 110 V / 115 V / 120 V / 127 Vac (settable via LCD)

100 V / 110 V / 115 V / 120 V / 127 Vac (settable via LCD) or 208 V / 220 V / 230 V / 240 Vac (settable via LCD)

Voltage regulation

± 1%

Frequency

Synchronized with utility in mains mode; 50 / 60 ± 0.2 Hz in battery mode

Waveform

Sinusoidal

Crest factor

3:1

Harmonic distortion

≤ 3% (linear load); ≤ 5% (non-linear load)

≤ 2%(linear load); ≤ 5% (non-linear load)

Transfer time

Mains mode to battery mode : 0 ms

Mains mode to battery mode: 0 ms

 

Inverter model to bypass mode: 4 ms (typical)

Inverter mode to bypass mode: 0 ms

Overload capability

105% ~ 150%: transfer to bypass in 30 s; 
> 150%: transfer to bypass in 300 ms

105% ~ 125%: transfer to bypass in 3 min;
125% ~ 150%: transfer to bypass in 30 s;
> 150%: transfer to bypass in 100 ms

EFFICIENCY

Mains mode

≥ 90%

≥ 92%

Battery mode

≥ 87%

≥ 91%

ECO mode

≥ 98%

≥ 98%

BATTERIES

DC voltage

24 V

48 V

72 V

192 V

Inbuilt battery of standard model

2 × 9 Ah

4 × 9Ah

6 × 9Ah

16 × 7 Ah

16 × 9Ah

Charging current

Standard model

1A

 

Long time model

6 A

1 A / 3 A / 5 A / 8 A

Recharge time

8 h

ALARM

Utility failure

Beep / 4 s

Battery low

Beep / 1 s

Overload

Beep twice / 1 s

UPS fault

Long beep

COMMUNICATIONS

RS232 (standard) /  USB

Supports Windows 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10

SNMP (option)

Power management from SNMP manager and web browser

OTHERS

Humidity

20 ~ 90% RH @ 0 ~ 40℃(non-condensing)

Noise level

≤ 50 dB (1 m)

≤ 55 dB (1 m)

Long backup time model

Dimensions (W × D × H) (mm)

440 × 468 × 88

440×580×132 (UPS)
440×580×132 (transfermer)

 

Packaged dimensions (W × D × H) (mm) 

530 × 590 × 170

511 × 683 × 192 (UPS)
511 × 683 × 192 (transfermer)

 

Net / Gross weight (kg)

6.0 / 7.5

12.0 / 13.5

13.0 / 14.5

16.5 (UPS)
49 (transfermer)

17 (UPS)
69 (transfermer)

Standard model

Dimensions (W × D × H) (mm)

440 × 468 × 88

440 × 690 × 88

440 × 580 × 132 (UPS) 
440 × 580 × 132 (transfermer)
440 × 580 × 132 (Battery)

 

Packaged
dimensions (W × D × H) (mm) 

530 × 590 × 170

530 × 825 × 170

511 × 683 × 192 (UPS) 
511 × 683 × 192 (transfermer)

511 × 683 × 192 (Battery)

 

Net / Gross weight (kg)

12.0 / 13.5

28.5 / 30.0

33.5 / 35.0

16.5 (UPS)

17 (UPS)

 

 

 

 

 

60 (Battery)

66.5 (Battery)

 

 

 

 

 

49 (transfermer)

69 (transfermer)

 
Pictures of this Online transformerless UPS HC900RT 1 kVA -10 kVA (120 V)
 
 

 

 
FAQ of this Online transformerless UPS HC900RT 1 kVA -10 kVA (120 V)
 
 
Certification of this Online transformerless UPS HC900RT 1 kVA -10 kVA (120 V)
 
Our service of this Online transformerless UPS HC900RT 1 kVA -10 kVA (120 V)
 
 
Classic case of this Online transformerless UPS HC900RT 1 kVA -10 kVA (120 V)
 
Looking forward to your inquiry for this Online transformerless UPS HC900RT 1 kVA -10 kVA (120 V)

LEAVE YOUR MESSAGES

Send Inquiry Now