Off grid solar inverter 120kVA

This Off-Grid solar system is available in 10 kVA ~ 120 kVA models with DSP digital control technology, it is combined with pulse-width modulation (SVPWM), disturbance MPPT control and multi-level control technology to enable the system to track the maximum power of solar panels fast. Its secure power supply feature provides good quality power with regulated voltage and frequency to the loads, and it is featured with energy storage and staggering power consumption as well. It is an ideal inverter for medium-sized or large-scale residential, commercial and industrial PV applications which are off the grid, such as village, farm, factory, office building and islands etc.


details

Description of this Off grid solar inverter 120kVA power inverter module
 
This Off-Grid solar system is available in 10 kVA ~ 120 kVA power inverter module with DSP digital control technology, it is combined with pulse-width modulation (SVPWM), disturbance MPPT control and multi-level control technology to enable the system to track the maximum power of solar panels fast. Its secure power supply feature provides good quality power with regulated voltage and frequency to the loads, and it is featured with energy storage and staggering power consumption as well. It is an ideal inverter for medium-sized or large-scale residential, commercial and industrial PV applications which are off the grid, such as village, farm, factory, office building and islands etc.
Features
● High-speed DSP digital control
● Full-bridge inverter control technology, providing secure power supply in the event of threephase 100% unbalanced loads
● Multi-string PV connected
● Inbuilt AC rectifier and MPPT control modules, configured battery parameters by operating interface, self-regulation for charging voltage and current
● Hot-swap MPPT modules for easy maintenance and power expansion
● Auto access MPP tracking states, be most probable to use PV energy in priority
● Intelligent AC and PV complementation power supply function to extend the battery life
● Using multicore control technology and auto MPP trackers, auto-start AC rectifier enable PV and AC source to supply power to the loads at the same time in the event of insufficient PV, which reduces battery discharge times and extend the battery life
● Intelligent staggering power consumption function
● Standard RS232, RS485 and optional SNMP communication port
● Multiple remote control: startup, shutdown, abnormal clearance, EPO, battery test and remote alarm port
● Staggering energy storage and power generation
2. Inverter operation sequence
1) Start the inverter operation sequence:
(1) Check if the inverter wiring is correct, all switches should be in the off state;
(2) Check if the DC 220V power supply is normal. After confirming the normal condition, make the mains input open in the “closed” state, and the inverter ship switch is in the “closed” state (because the mains priority is given, the “mains” indicator light is on, AC The output should have 220VAC output. When the mains is cut off, the system will automatically switch to the inverter output state, the “inverter” indicator will be on, and the AC output will be normal).
(3) Check whether the various meters, indicators and fans are working properly;
(4) When the load is turned on, it can operate normally.
2) Turn off the inverter operation sequence:
(1) cutting off the AC output circuit;
(2) cut off the mains input;
(3) Cut off the 0 and 1 switches;
(4) Cut off the DC input circuit.
 
Specification of this Off grid solar inverter 120kVA
 

MODEL

10KVA

20 kVA

30 kVA

40 kVA

60kVA

80 kVA

100 kVA

120 kVA

Rated power(KW)

9 kW

18 kW

27 kW

36 kW

54 kW

72 kW

90 kW

108 kW

Rated current(A)

15 A

30 A

45 A

60 A

91 A

120 A

152 A

182 A

Output power factor

0.9

Rated input voltage

380 Vac ± 20%

Rated output voltage

380 Vac± 1%

Battery voltage

360 Vdc

Number of battery

12Vdc×30 pcs / 2 Vdc×180 pcs

Operating mode

AC and PV complementation

PV INPUT

Max. voltage (Voc)

750 Vdc

Optimum operating voltage (Vmp)

450 ~ 550 Vdc

Max.conversion efficiency

≥ 98%

Floating charge voltage (25℃)

414 Vdc ± 1%

Equalizing charge voltage (25℃)

428 Vdc ± 1%

MPPT Max. current

60 A

120 A

180 A

240 A

300 A

Max. PV power

25 kW

2 × 25 kW

3 × 25 kW

4 ×25 kW

5× 25 kW

Number of PV input

1

2 + 1 (reserve)

3 + 1 (reserve)

4 + 2 (reserve)

5 +3 (reserve)

MPPT modules

1

2 + 1 (reserve)

3 + 1 (reserve)

4 + 2 (reserve)

5 + 3 (reserve)

AC RECTIFIER

Input voltage range

380 V ± 20% three-phase

Rated frequency

50 Hz / 60 Hz ± 5 Hz (settable)

Power factor

0.8

Floating charge voltage (25℃)

410 V ± 1%

Equalizing charge voltage (25℃)

415 V ± 1%

Max. charging current

12 A

25 A

38 A

50 A

75 A

167 A

208 A

250 A

INVERTER

Inverter voltage

380 Vac three-phase + N+PE

Phase voltage

220 / 230 / 240 Vac (settable)

Output voltage precision

± 1%

Transient voltage range

± 5%

Transient recovery time

20 ms

Rated frequency

50 Hz / 60 Hz ± 1 Hz (settable)

Frequency tracking range

50 Hz / 60 Hz ± 3 Hz

Peak factor

3:1

Waveform

Sinusoidal

Waveform distortion

≤ 3% (linear load)

Voltage unbalance

± 3% (100% unbalanced load)

Overload

≥ 105% ~ 110%: 1 hour to bypass, automatic recovery of load shedding; ≥ 110% ~ 125%: 10 minutes to bypass, automatic recovery of load shedding; ≥ 125% ~ 150%: 1 minute to bypass, minus Automatic recovery; ≥150%: 10 seconds after the system shuts down directly, the user confirms the load shedding; ≥200%: The system immediately shuts down, the user confirms the load shedding

Shortcircuit

≥ 125% ~ 150% for 1 min;

Max. efficiency

≥ 90%

≥ 91%

≥ 92%

≥ 93%

BYPASS

Rated voltage(V)

380 Vac three-phase + N+PE

Voltage range

± 20%

Rated frequency

50 Hz / 60 Hz ± 5 Hz

Max. current

19 A

38 A

57 A

76 A

114 A

152 A

190 A

228 A

BATTERIES MANAGEMENT

EOD voltage settings

1.58 Vdc ~ 1.83 Vdc (settable), 1.75 Vdc (default)

Staggering DOD (Depth of Discharge) settings

1.85 Vdc ~ 2.1 Vdc (settable), 1.89 Vdc (default)

Charging current settings

Factory default 0.15 C10; 0.07 ~ 0.3 C10(settable)

Battery management

Auto-transfer between equalizing charge and floating charge; Auto- temperature compensation of batteries

TRANSFER TIME

Inverter – Bypass

0 ms

Bypass – Inverter

0 ms

COMMUNICATIONS

Remote control

Inverter startup, shutdown, abnormal clearance, EPO, battery self-test

Communication interface

RS232, RS485, SNMP (optional)

Dry contacts output

Bypass input abnormal, rectifier input abnormal, system fault, system alarm, low battery, output overload, fan fault, generator ON / OFF

OTHERS

Operating temperature

0℃~ 40℃

Max. relative humidity

90% (non-condensing)

Max. altitude

1000 m at rated power (derating 1% for each additional 100 m); Max. 4000 m

Noise level at 1 m (dB)

≤ 65 dB (varies with loads and temperature)

IP rating(EN60529)

IP20

Dimensions (W × D × H) (mm)

450 × 840 × 1100

600 × 700 × 1750

960 × 800 × 1700

Packaged dimensions (W×D×H) (mm)

530 × 920 × 1140

690 × 790 × 1850

1040 × 890 × 1750

Weight (kg)

230

245

380

430

515

760

800

860

MODEL

HC3000

HC4000

HC3000

HC5000

HC6000

HC8000

Rated power

3 kW

4 kW

3 kW

5 kW

6 kW

8 kW

Battery voltage

96 Vdc

192 Vdc

Operating mode

PV priority / AC priority(Optional)

PV INPUT

Input voltage range

96 ~ 200 Vdc

192 ~ 400 Vdc

Max. charging current

10 ~ 60 A (selectable)

10 ~ 40 A(selectable)

10 ~ 60 A (selectable)

Optimum operating voltage (Vmp)

120 ~ 142 Vdc

240 ~ 284 Vdc

Max. PV frequent (Pmax)

5760 W

7680 W

11520 W

Max. conversion efficiency

98%

AC INPUT

Input voltage

165 ~ 275 Vac

Input frequency

40 ~ 70 Hz (overclocking: auto transfer to DC power supply)

Output voltage

220 Vac ± 5%

Input power factor

≥ 0.8

Max. efficiency

88% (online mode)

Max. charging current

8 A

12 A

Short circuit

Current-limiting, transfer to bypass; air circuit-breaker

INVERTER OUTPUT

Output voltage

220 Vac ± 5%

Output frequency

50 Hz / 60 Hz ± 1% (auto-sense)

Waveform

Sinusoidal

Output power factor

1

Waveform distortion

≤ 5% (linear load)

Transfer time (PV – AC)

0 ms

Max. efficiency

92%

Short circuit

Current-limiting, transfer to bypass or system auto shutdown

ALARMS

Utility power abnormal

4 s per beep , auto mute in 40 s

Low battery

0.2 s per beep

Overload

1 s per beep

COMMUNICATIONS

Communication interface

RS232, USB, RS485, SNMP (optional)

Dry contacts

PV fault, low battery, overload, bypass, inverter fault, generator ON / OFF

OTHERS

Overload protections

110% for 255 s; 125% for 60 s; 150% for 10 s

Wiring

Terminal blocks

EMI

EN62040-2:2006; EN61000-3-2:2006; EN61000-3-3:2008

IP rating

IP20

Ambient temperature

0℃ ~ 40℃

Relative humidity

10% ~ 90% (non-condensing)

Noise

≤ 50 dB

Operating altitude

2000 m (derating 1% for each additional 100 m)

Dimensions (W × D × H) (mm)

560 × 265 × 725

Packaged dimensions (W × D × H) (mm)

662×360 × 905

Net weight (kg)

76

80

60

67

69

85

Gross weight (kg)

85

89

69

76

78

94

 
Pictures of this Off grid solar inverter 120kVA
 
 
FAQ of this Off grid solar inverter 120kVA
 
 
Certification of this Off grid solar inverter 120kVA
 
Our service of this Off grid solar inverter 120kVA
 
 
Classic case of this Off grid solar inverter 120kVA
Looking forward to your inquiry for this Off grid solar inverter 120kVA